- Fast Frequency Response (FFR), sub-second power adjustment following frequency table
- Frequency Containment Reserve (FCR), ~second power adjustment following frequency table
- Automatic Frequency Restoration Reserve (aFRR), ~second energy production following TSO setpoint signal
- Manual Frequency Restoration Reserve, ~minute energy production following TSO activation signals
My understanding is the primary failure in Spain was that 9 separate synchronous plants that had sold aFRR(?) to the TSO then failed to deliver, so when the TSO algorithms tried to adjust the oscillations, nothing happened. Everything else was kinda "as designed".